e1210-iologik-ethernet-remote-i-o.png

Giới thiệu dòng thiếu bị Iologik Moxa

IoLogik E1210 Ethernet remote I/O with 2-port Ethernet switch, 16 DIs

 

Features and Benefits 

  • User-definable Modbus/TCP Slave addressing
  • Supports EtherNet/IP* adapter mode
  • Supports RESTful API for IIOT applications
  • 2-port Ethernet switch for daisy-chain topologies
  • Save time and wiring cost with peer-to-peer communications
  • Active communications with MX-AOPC UA Server
  • Supports SNMPv1/v2c
  • Easy mass deployment and configuration with ioSearch utility
  • Friendly configuration via web browser
  • Simplify I/O management with MXIO library on either a Windows or Linux platform
  • Class I Division 2, ATEX Zone 2 certification
  • Wide operating temperature range: -40 to 75°C (-40 to 167°F) 
    *Requires online registration (available free of charge)

Introduction

I/O to IT/OT Protocol Conversion

The ioLogik E1200 does just what you need by supporting the most often-used protocols for retrieving I/O data. Most IT engineers use SNMP or RESTful API protocols, but IA engineers are more familiar with Operational Technologies (OT), such as Modbus and EtherNet/IP. Moxa's Smart I/O makes it possible for both IT and IA engineers to conveniently retrieve data from the same I/O device. The ioLogik E1200 series speaks six different protocols, including Modbus/TCP, EtherNet/IP, and Moxa AOPC for IA engineers, as well as SNMP, RESTful API, and Moxa MXIO library for IT engineers. The ioLogik E1200 retrieves I/O data and converts the data to any of these protocols at the same time, allowing you to get your applications connected easily and effortlessly. Learn more…


Daisy-chained Ethernet I/O Connection

A new daisy-chained Ethernet I/O concept is now available. The ioLogik E1210 industrial Ethernet remote I/O has two embedded Ethernet switch ports that allow information to flow to another local Ethernet device or connect to the next ioLogik in the daisy-chain.

Applications such as factory automation, security and surveillance systems, and tunnel monitoring, can make use of daisy-chained Ethernet for building multi-drop I/O networks over standard Ethernet cables. Many industrial automation users are familiar with the multi-drop configuration typically used in fieldbus applications. The daisy-chain function on the Ethernet remote   I/O ioLogik E1210 not only increases the connection between machines and panels, but also lowers the cost of buying separate Ethernet switches, and at the same time reduces labor fees and cabling by a large percentage. For example, if a production facility contains 700 stations (20 points per station), the wiring cost reduction can reach 15% of the total implementation cost.

 

Saving Time and Wiring Costs with Peer-to-Peer Communications

In remote automation applications, the control room and sensors are often far removed, making wiring over long distances a constant challenge. With peer-to-peer networking, users may now map a pair of ioLogik E1200 series modules so that input values will be directly transferred to output channels, greatly simplifying the wiring process and reducing wiring costs.

 

 

User-definable Modbus/TCP Addressing for Painless Upgrading of Existing Systems

For Modbus devices that are controlled and detected by fixed addresses, users need to spend a vast amount of time researching and verifying the configurations. Users need to locate each device’s networking details like I/O channels, or vendor-defined addresses to enable the initial or start address of a SCADA system or PLC. The ioLogik E1200, with user-definable Modbus/TCP addressing, offers greater flexibility, and setup is easy. Instead of worrying about individual devices, users simply configure the function and address map to fit their needs.

 ioLogik E1210 Specifications

• Inputs and Outputs

Digital Inputs

16 channels

Isolation

3k VDC or 2k Vrms

• Digital Input

Sensor Type

Wet Contact (NPN or PNP), Dry Contact

I/O Mode

DI or Event Counter

Dry Contact

• On: short to GND
• Off: open

Wet Contact (DI to COM)

• On: 10 to 30 VDC 
• Off: 0 to 3 VDC

Common Type

8 points per COM

Counter Frequency

250 Hz

Digital Filtering Time Interval

Software configurable

• Power Requirements

Input Voltage

12 to 36 VDC

Input Current

110 mA @ 24 VDC

• MTBF (mean time between failures)

Time

671,345 hrs

Standard

Telcordia SR332

• Common Specifications

• LAN

Ethernet

2 switched 10/100 Mbps RJ45 ports

Protection

1.5 kV magnetic isolation

Protocols

Modbus/TCP (Slave), EtherNet/IP*, SNMPv1/v2c, RESTful API, TCP/IP, UDP, DHCP, BOOTP, HTTP

*Requires online registration at https://www.moxa.com/Event/DAC/2016/Smart_EIP_IO/index.htm (available free of charge) 

• Physical Characteristics

Wiring

I/O cable max. 14 AWG

Dimensions

27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)

Weight

Under 200 g (0.44 lb)

Mounting

DIN rail or wall

• Environmental Limits

Operating Temperature

Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Ambient Relative Humidity

5 to 95% (non-condensing)

Shock

IEC 60068-2-27

Vibration

IEC 60068-2-6

Altitude

Up to 2000 m

Note

Please contact Moxa if you require products guaranteed to function properly at higher altitudes.

• Standards and Certifications

Safety

UL 508

EMC

EN 55032, EN 55024, EN 61000-3-2/3-3, EN 61000-6-2/6-4

EMI

CISPR 32, FCC Part 15B Class A

EMS

IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8

Hazardous Location

Class 1 Division 2, ATEX Zone 2

Green Product

RoHS, CRoHS, WEEE

Note

Please check Moxa’s website for the most up-to-date certification status.

• Warranty

Warranty Period

5 years

Details

See www.moxa.com/warranty

Note

Because of the limited lifetime of power relays, products that use this component are covered by a 2-year warranty.